2023年1月31日,美國EPA發(fā)布了計算機服務器能源之星4.0版本的最終草稿版,并公布此版本將于2024年1月12日正式生效,
4.0版最終草稿相比3.0版更新如下:
更新一:
在產(chǎn)品類型中增加了Storage Heavy Server (SHS)和Hyperconverged Server這兩個新的類別的定義(備注:SHS定義中的存儲設備必須是內部存儲設備。),但是目前暫未將Hyperconverged Server列入需要能源之星認證的名單。
Storage Heavy Server (SHS): A computer server with greater storage capacity than a standard computer server. As shipped, these computer servers support 30 or more storage devices. These servers differ from Storage Products in that they run computer server operating systems and software stacks.
Hyperconverged Server: A highly integrated server which contains the additional features of large network equipment and storage products
更新二:
更新了電源模塊的能效要求。
原3.0版本要求,所有輸出功率采用相同的能效要求:
Table 1: Efficiency Requirements for PSUs
| Power Supply Type | Rated Output Power | 10%Load | 20%Load | 50%Load | 100%Load |
| Multi-output(Ac-Dc) | All Output Levels | N/A | 90% | 92% | 89% |
| Single-output(Ac-Dc) | All Output Levels | 83% | 90% | 94% | 91% |
4.0版本把電源輸出以750W為界限劃定了不同的能效要求:
Table 1: Efficiency Requirements for PSUs4
| Power Supply Type | Rated Output Power(W) | 10%Load | 20%Load | 50%Load | 100%Load |
| Multi-output(Ac-Dc) | 750 watts or greater | N/A | 90% | 92% | 89% |
| Single-output(Ac-Dc) | Less than 750 watts | N/A | 87% | 90% | 87% |
| Single-output(Ac-Dc) | 750 watts or greater | 90% | 94% | 96% | 91% |
| Power Supply Type | Rated Output Power(W) | 10%Load | 20%Load | 50%Load | 100%Load |
| Multi-output(Ac-Dc) | Less than 750 watts | 83% | 90% | 94% | 91% |
更新三:
更新了并提高了計算機服務器的活動狀態(tài)效率閾值的要求。
原3.0版本對于所有計算機服務器的活動狀態(tài)效率閾值要求:
Table 3: Active State Efficiency Thresholds for all Computer Servers
| Product Type | Minimum EffAcTIV |
| One Installed Processor | |
| Rack | 11.0 |
| Tower | 9.4 |
| Blade or Multi-Node | 9.0 |
| Resilient | 4.8 |
| Two lnstalled Processors | |
| Rack | 13.0 |
| Tower | 12.0 |
| Blade or Multi-Node | 14.0 |
| Resilient | 5.2 |
| Greater Than Two Installed Processors | |
| Rack | 16.0 |
| Blade or Multi-Node | 9.6 |
| Resilient | 4.2 |
4.0版本中對于非大容量服務器的活動狀態(tài)效率閾值要求:
Table 3: Active State Efficiency Thresholds for all non-SHS Computer Servers
| Product Type | Minimum EffAcTIV |
| One Installed Processor | |
| Rack | 26.4 |
| Tower | 24.4 |
| Resilient | 6.6 |
| Two lnstalled Processors | |
| Rack | 30.4 |
| Tower | 26.5 |
| Blade or Multi-Node | 29.1 |
| Resilient | 6.0 |
| Greater Than Two Installed Processors | |
| Rack | 31.9 |
| Blade or Multi-Node | 26.8 |
我們秉承科學嚴謹?shù)墓ぷ鲬B(tài)度,以客戶為中心,高效統(tǒng)籌安排測試計劃,竭力縮短測試時間的周期,為客戶提供快捷、公正的第三方咨詢檢測等服務。服務區(qū)域遍布廣東廣州、深圳、東莞、佛山、中山、珠海、清遠、惠州、茂名、揭陽、梅州、江門、肇慶、汕頭、潮州、河源、韶關及全國各地如您有相關產(chǎn)品需要咨詢,歡迎您直接來18165787025咨詢我司工作人員,獲得詳細的費用報價與周期方案等信息,深圳訊科期待您的光臨!
上一篇:SVHC清單新增9項候選物質
下一篇:阿聯(lián)酋TDRA更新型式認證標簽要求
- 手術無影燈照度均勻性測試(50000h后)
- 訊科解讀:注射泵阻塞報警壓力全量程測試要點與規(guī)范
- 訊科技術剖析:電子體溫計探頭響應時間測試(35-42℃)的專業(yè)方法論與應用價值
- 血氧飽和度探頭光路偏移測試(機械沖擊后)
- 訊科標準檢測:血壓計袖帶粘扣剝離強度 1000 次測試規(guī)范解析
- 訊科檢測解析:輸液泵流量精度測試(全流速范圍)的意義與方法
- 訊科技術聚焦:醫(yī)用監(jiān)護儀心電導聯(lián)線5萬次抗彎折測試解析與可靠性評估
- 超聲波探頭聲透鏡耦合劑浸泡老化測試與可靠性評估——訊科標準檢測
- 訊科檢測:滑雪鏡鏡片冷熱交替防霧測試技術解析
- 訊科技術解析:潛水手電筒100米深度壓力測試與密封可靠性評估